Choosing a UPS comes down to four separate decisions. Use this guide to prepare your requirement, then ask an APS engineer to confirm it on site.

1. Load

List every device the UPS will power and note its wattage from the nameplate or datasheet. If only amps are given: watts = volts × amps (230 V for single-phase). Add them up.

2. Capacity

Convert watts to kVA using the UPS power factor (kVA = watts ÷ (power factor × 1000)), then keep your load at about 70–80% of the UPS rating. Example: a 1,220 W load on a unity-power-factor UPS needs about 1.6 kW, so a 2 kVA unit fits.

3. Runtime

Backup time depends on the battery bank — battery Ah and the number of batteries — not on the kVA rating. Tell us how many minutes you need at your load and we will size the batteries.

4. Expansion

Plan for growth and redundancy. An N+1 design or a modular UPS such as the Liebert APM Plus lets you add power modules later without replacing the system.

Which UPS category fits the site?

Single-phase online UPSThree-phase online UPSLarge and modular UPS
Capacity600 VA – 20 kVA10 – 80 kW50 – 1,200 kW
Example modelsLiebert ITON CX, ITA2, GXT MT+Liebert ITA2 5–30 kVA, S600E / S600D, EXSLiebert APM Plus, EXM2, EXL S1, HiPulse U
Typical sitesOffices, clinics, retail, network and server racksHospitals, labs, factories, larger server roomsData centres, hospital campuses, process plants
Form factorTower or rackTower; isolation-transformer optionsModular frames for N+1 growth

Capacity ranges are the Vertiv models listed on apstechsystems.com. Confirm the exact model with an APS engineer.

Quarterly maintenance checklist

  • Visual and cleaning — dust removal, fans and vents, signs of heat or damage
  • Connections — tighten terminals; thermal check for hot spots
  • Batteries — voltage, condition and a backup-time check
  • Alarms and logs — review event history and active alarms
  • Load and bypass — measured load against rating; bypass readiness
  • Report — findings, actions taken and recommended next steps